KBS Coating Australia, Fire Protection System, Cable Spraying, Cable Coating Australia, KBS Coating Installer, Fire Stop System, Painting Contractors, Fireproofing, Penetration Seals, Fireproofing Spray

Friday, November 26, 2010

Trend of Cable Penetration Seals for Fire Proofing

Posted by Fire Protection Coatings on 12:59 AM 1 comments

As per invention of technology ways of Fire Stop System are also altered. Here we will trash out the Cable Penetration Seals – widely adaptable fireproofing system. 

Penetration Seals
In the industrial area use of cable is very normal so cables located in the plant present a risk for room to room fire, smoke as well as gas transfer. So, Penetration Seals segment provides protection to the area from fire chain reaction. 

KBS cable penetration seals offer reliable protection in the spread of fire and smoke. The KBS Panel Seal is a Cable Penetration Seal consisting of non-combustible mineral fibre boards combined with ablative products (ABL) or – alternatively – with intumescent products (INT)

There are 3 types of Penetration Seals as following:

 - KBS Panel Seal: It is single as well as double panel seals for fire-resistant cable penetrations
 - KBS Panel Seals: They are used to close through-penetration fire-stops for cables and cable trays in walls   and floors, smoke-gas tight and fire-resistant
 - KBS Coating with combination of KBS Sealant is used for the KBS Panel Seal ABL

Moreover, KBS Foamcoat and the corresponding putty KBS® Foamcoat C11 are employed for the intumescent type KBS Panel Seal INT. Cable panel seal can be installed as single-panel or as double-panel seal depending on the requirements with regard to fire resistance. The Penetrating Cables and trays as well as the visible surfaces of the mineral fibre boards are coated in accordance with the corresponding national tests/approvals.



Features of Cable Penetration Seals Provider


  - Able to pull new or remove old cables and easily reinstall the designed Fire Protection System
 - Offers completed work insuring correct installation. 
 - Design drawings are assembled to allow each step of the process that enables to be understood by a novice installer. 
 - Able to offer corrective maintenance which can be performed 10, 20, even 30 years from now. 
 - System designs are installed by SRE’s trained and certified installers. 
 - Ability to install while the unit is live as well as to accommodate openings up to 6’’ in diameter. 

There are many physical and online sources which offer Cable Fire Protection Australia, Fireproofing or Intumescent Mastic Paint, Cable Spraying, Painting Contractors, Fireproofing Spray and many more. So, you can select the proper Cable Penetration Seals provider as per your need.

For more information about services as well as diverse products please do visit: http://www.robertsoncoatings.com.au
Continue...


Thursday, November 18, 2010

Fireproofing Spray -- A New Trend of Fire Stop System

Posted by Fire Protection Coatings on 2:25 AM 6 comments

We know that Cable Fireproofing is done with many kinds of tactics. But here you will be known its spray tactic means features of  Fireproofing Spray and what you should keep in mind before going with Cable Spraying provides. Moreover, you can also come to know about different fireproofing spray equipment.



Cable Fireproofing by spray is done in the conventional way by spraying crosswise. Cable Coating through Fireproofing Spray cover the color of the cable jacket. In this coating wet thickness of the coating must be at least 2.5 mm on all exposed sides. Moreover, if you want at hard to- get- at places then an extension nozzle use is advised. In case when cables are close to a wall then stuff mineral wool between cables and wall will be coat over. Further, needed thickness may be applied in one coat.

KBS Fireproofing Spray Coating may be applied with a great variety of spray equipment; however, good results can be obtained with the following:


Airless Spray Equipment:

 - Graco Ultra 1500 Mark V
 - Pressure at gun: 0-200 bar
 - Spray gun orfice: 0.9-1.0

      Conventional Spray Equipment:

       - With pressure pot - Binks, De Vilibis Mastic,    Wally or STA
       - Material pressure: 4-5 bar
       - Pressure at gub: 4 bar
       - Spray gun orifice: minimum 3 mm diameter
       - Material hose: minimum 3/4” diameter

          In the next step we should take a look for material used for Fireproofing Spray and it's important to do diligent research before choosing a brand OR a provider. Usually, spray applied fireproofing is cost effective so it is accepted by large amount of user. Further, in these days spray on cementitious fireproofing is becoming one of the most common materials to use as it is cheap, efficient and easy to apply.

          Moreover, different building materials of fireproofing spray won't all respond alike to the same type of fireproofing. So, it is very important when doing your research to make sure that you learn what brand/type of fireproofing material will work best for your structure.

          Features:

           - Water-based: To offers easy installation and cleanup.
           - Thixotropi: To provide easy installation as well as cleanup.
           - Auto bonding and Flexible
           - No solvents and No asbestos so safe.
           - Non-halogenated and Weather Resistant
           - Low Abrasion: To offer longer pump life with less maintenance.
           - Factory Mutual tested as well as approved.

          So, if you are looking for any cost effective Cable Fireproofing then Cable Spraying is the great.

          Robertson Coatings has been established in 2004. It is a diversified company specialized in offer commercial, Cable Coating Australia, KBS Coating, Mastic paint, fire paints, intumescent coating Interior Fireproofing, maintenance painting and many more. For more information about services as well as diverse products please do visit: http://www.robertsoncoatings.com.au

          Continue...


          Saturday, November 13, 2010

          Fire Protection with KBS Cable Coating

          Posted by Fire Protection Coatings on 1:42 AM 1 comments

          We know that fire incidents can be occur anytime so usually we always follow basic or pioneer Fire Stop System to cope up with such fire incidents. Today, cable is one of the applicable objects to any kind of business so its Fire Protection is also required. So, here we will discuss about the different ways of Cable Coating Application.

          Cables are in pioneer need of this technology world and if we think about the Fire Protection then cables are not exceptions from this. Usually KBS Coating is a water-based fire protective coating which is invented for offering the Fire Protection to group or bundled electrical cables as well as to Penetration Seals.

          Moreover, the main function of  KBS Coating is to stop flame circulation along vertical as well as horizontal cable ways. Additionally where circuit integrity depends on the distance of the cables from fire and the incurred temperature that time KBS Coating can delay short circuit.

          KBS Coating shields electrical cables via ablation instead of insulation. Further, it is dense as well as thermally conductive in duration of normal cable operating temperatures. There are different ways for applying the KBS Coating so, take a look to these methods.

          Surface Preparation
          In this cleaning of cables is not required but oil or grease should be removed with dry rags (no solvent). Use of broom or vacuum cleaner is advisable to remove heavy layers of dust.

          Spray
          This Fire Protection is done in the conventional way by spraying crosswise. In such type of application white of the coating should well cover the color of the cable jacket and the wet thickness of the coating must be at least 2.5 mm on all exposed sides. Normally, the required thickness may be applied in one coat.

          Brush:  
          Cable Coating through the brushing application requires numerous coats to build up the required thickness. Further, a thin coat applied first and then allowed to dry will aid in building up the required thickness.

          Hand:
          This Cable Coating tactic is adaptable in large diameter single cables or bundles; however, to achieve a smooth finish use of wet brush is advised. Moreover, thin coat should be allowed to dry before the rest is applied, using both hands like an extrude.

          Robertson Coatings has been established in 2004. It is a diversified company specialized in offer commercial, Cable Coating Australia, KBS Coating, Mastic Paint, intumescent coating Interior Fireproofing, maintenance painting and many more.

          For more information about services as well as diverse products please do visit: http://www.robertsoncoatings.com.au
          Continue...


          Related Posts with Thumbnails